Instrumentation cables for signal and
switching polyethylene Insulated: BS5308 PART 1.
The constructions are categorised
as follows:-
Construction:
Type 1 Unarmoured
Conductor: Stranded or Solid
Plain Annealed Copper,
Insulation: Polyethylene, Laying Up: Cores Twisted
together in pairs, Binder tape: PETP Transparent tap, Screen:
aluminium Backed Polyester Tape in Continuous Contact with Tinned
Copper Drain Wire.
NB (Screens can be as follows - Individual, Individual and
Collective or just collective). Sheath: PVC RP Blue or
Black.
|
Type 2 Armoured
Conductor:
Stranded or Solid Plain Annealed Copper
Insulation: Polyethylene, Laying Up: Cores twisted
together in pairs, Binder Tape: PETP transparent Tape,
Screen: Aluminium Backed Polyester tape in continuous contact
with tinned copper drain wire.
NB (screens can be as follows - individual, individual and
collective or just collective). Bedding: Polyethylene,
Armour: Galvanised steel wire Armour, Sheath: PVC RP Blue
or Black.
|
Type 3 Lead Sheath & Armoured
Conductor:
Stranded or Solid Plain Annealed Copper,
Insulation: Polyethylene, Laying Up: Cores Twisted
together in pairs, Binder Tape: PETP Transparent Tape,
Screen: Aluminium Backed Polyester Tape in Continuous Contact
with Tinned Copper Drain Wire.
NB (screens can be as follows - individual, individual
and collective or just collective). Bedding: PVC, Sheath:
Lead Alloy, Bedding: PVC, Armour: Galvanised Steel Wire Armour,
Sheath: PVC RP Blue or Black.
|
Application:
These cables are designed
for connection to electrical instrument circuits and provide communication
services in process plants water treatment and chemical plants.
The armoured versions are suitable for direct burial.
|
Technical Data:
Voltage 300/500V
Test Voltage: 1000V
Operating Temperature Range: 0oC to +70 oC installation
-40°C to +70°C fixed
|
|
Also available with LSF Sheath.
Generally constructions of 2,5,10,20
apply to the range in 0.5SQMM, 0.75SQMM and 1.55SQMM conductor
size.
PVC Insulated: BS5308 PART 2
Construction:
|
|
Type 1 Unarmoured
Conductor: Stranded or Solid
Plain Annealed Copper,
Insulation: PVC, Laying up: Cores Twisted together
in pairs,
Binder type PETP Transparent Tape, Screen: Aluminium Backed
Polyester tape in Continuous Contact with Tinned Copper Drain
Wire. NB (Screens can be as follows - Individual, Individual
and Collective or just Collective).
Sheath: PVC RP, Blue or Black.
|
|
Type 2 Armoured
Conductor: Stranded or Solid
Plain Annealed Copper,
Insulation: PVC, Laying Up: Cores Twisted together
in Pairs, Backed Polyester Tape in Continuous Contact with Tinned
Copper Drain Wire. NB(Screens can be as follows - Individual,
Individual and Collective or just Collective).
Bedding: PVC. Armour: Galvanised Steel Wire Armour,
Sheath: PVC RP, Blue or Black
|
|
Application:
These cables are designed for connection
to electrical instrument circuits and provide communication services
in process plants water treatment and chemical plants. The armoured
versions are suitable for direct burial.
|
|
Technical Data:
Voltage: 300/500V
Test Voltage: 1000V
Operating Temperature range: 0oC to +70oC installation
-40°C to 70°C fixed.
|
|
Also Available with LSF sheath.
Generally constructions of 2,5,10,20
Pairs apply to the range in 0.5SqMM, 0.7SQMM and 1.5SQMM conductor
size.
|
|
ESI 09-6
Screened PVC solid conductors of
0.8MM DIA or 0.9MM DIA laid up within foil screen and drain. Black
PVC outer Jacket. These cables are 200 and 100 paired respectively
and according to conductor size.
|
|
CW1128/1198
Poly Jel filled polyethylene insulated,
0.5MM DIA and 0.9MM DIA, unarmoured and armoured telephone cables up to 100 pairs for external
installation
|
|
CW1308
PVC insulated and sheathed internal
telephone cables, available in 'LSF' version. 0.5MM DIA conductors
in pairs up to 320 pair. Also available is CW1308B external/internal
with a moisture barrier in 'LSF'. Please enquire
for more details.
|
|
"Special Cables are standard stock at
Harpers".
|